6RA7086-6KV62 6RA70866KV62
SIMOREG DC-MASTER chassis converters 6RA70 for four-quadrant operation (B6)A (B6)C 3-ph. 690VAC
Rated supply voltage armature V |
3-ph. AC 690 (+10% / –20%) |
Rated input current armature A |
630 |
Rated supply voltage electronics supply V |
2-ph. AC 380 |
Rated supply voltage field V |
2 AC 460 (+15 % / -20 %) |
Rated frequency Hz |
45 to 65 |
Rated DC voltage ) V |
830 |
Rated DC current A |
760 |
Overload capability |
Max. 1.8 times rated DC current |
Rated output kW |
551 |
Power loss at rated DC current (approx.) W |
2850 |
Rated DC voltage field V |
Max. 375 |
Rated DC current A |
30 |
Operational ambient temperature °C |
0 to 40 at rated ) separately cooled |
Storage and transport temperature °C |
–25 to +70 |
Installation altitude above sea level |
≤1000 m at rated DC current ) |
Dimensions (H x W x D) mm |
700 x 268 x 362 |
Weight (approx.) kg |
45 |
Rated supply voltage fan V |
3-ph. AC 400 (±15 %) 50 Hz |
Nominal fan current A |
0.3 |
Air flow rate m3/h |
570 |
Fan noise level dBA |
73 |